| Manufacturer |
CHAUVIN ARNOUX |
| Manufacturer Part No. |
C.A 6113 |
| Type of meter |
appliance meter |
| Kind of display used |
LCD 5,7" |
| Display resolution |
320x240 |
| Earthing resistance measuring range |
500mΩ...40Ω/15kΩ/40kΩ |
| Earthing resistance measuring accuracy |
±(2% + 2 digit) |
| Continuity test |
acoustic indication, optical indication |
| RCD test |
AC, A and F-type RCDs, general purpose |
| Loop impedance measurement |
100...500mΩ/4Ω/40Ω/400Ω |
| Measurement |
AC current (with current clamps), AC voltage, continuity, DC voltage, earthing resistance, frequency, impedance, insulation resistance, leakage current, phase sequence, RCD tripping current, RCD tripping time, short circuit loop impedance, votlage drop |
| Insulation resistance measuring ranges |
0.01MΩ...2GΩ |
| Test voltage |
50V/100V/250V/500V/1kV |
| IP rating |
IP53 |
| Conform to the norm |
CAT III 600V CAT IV 300V EN 61010 IEC 61326-1 |
| Body dimensions |
280x190x128mm |
| Weight with battery |
2.2kg |
| Illumination |
yes |
| Loop impedance measuring accuracy |
±(5% + 2 digit) |
| Power supply |
rechargeable battery Ni-MH x1 |
| Measuring instrument features |
long operating time up to 24 hours, programmable alarm thresholds, test leads resistance compensation |
| Standard equipment |
3 crocodile clips, carrying case, hand strap, mains battery charger, neckstrap, remote probe, screen protector preventing scratching (set), test leads, test probes |
| Optional equipment |
CA-C177, CA-C177A, CA-MN77 |
| Battery/ rechargeable battery |
rechargeable battery Ni-MH x1 |
| Gross weight |
2.2 kg |
| EAN code |
3760171418413 |