| Manufacturer |
FLUKE |
| Manufacturer Part No. |
FLUKE-725/FPC EU |
| Type of meter |
calibrator |
| Kind of calibrator |
current, frequency, pressure, RTD, thermocouple, voltage |
| Kind of display used |
LCD |
| DC voltage measuring range |
0...100mV/0...30V |
| DC voltage measuring accuracy |
±(0.02% + 2 digit) |
| DC current measuring range |
0...24mA |
| DC current measuring accuracy |
±(0.02% + 2 digit) |
| Resistance measuring range |
10mΩ...400Ω/1.5kΩ/3.2kΩ |
| Resistance measuring accuracy |
±(0.1%+1Ω) |
| Ω simulation |
15...3200Ω |
| Voltage source |
0...20V |
| Voltage source accuracy |
±(0,02% + 2 digits) |
| Current source accuracy |
±(0,025% + 1 digit) |
| Current source |
0...24mA |
| Dimensions |
200x96x47mm |
| Measurement |
DC current, DC voltage, resistance |
| Protection |
short circuit protection SCP |
| Illumination |
yes |
| Power supply |
battery LR6 AA 1,5V x4 |
| Measuring instrument features |
24V, 22mA loop supplying, automatic and manual step setting, automatic linear sourcing, measures and sources frequency within 1 cycle/min. to 10kHz range, measures and sources signals simultaneously from 2 channels, measures pressure up to 700 bar using any FLK-700Pxx pressure module, operates with 7 types of RTDs: Pt100 (385), Pt200, Pt500, Pt1000 (385), Pt100 (3916), Pt100 (3926), Ni120, operates with thermocouple types: J, K, T, E, R, S, B, L, N, U, XK, BP, settings memory |
| Standard equipment |
crocodile clips FLK-AC72, FLK-TL75 test leads, Fluke Premium Care- 1 year, set of test leads with alligator clips |
| Battery/ rechargeable battery |
battery LR6 AA 1,5V x4 |
| Gross weight |
1.26 kg |
| EAN code |
195112123638 |